| Model | FH-29900T | FH-30000T | FH-40000T | FH-50000T | FH-60000T |
|---|---|---|---|---|---|
| Inverter Input / Output Grid | |||||
| Rated Power | 29.9kW | 30kW | 40kW | 50kW | 60kW |
| Rated Voltage | 380 / 400Vac, 3W + N + PE | ||||
| Rated Frequency | 50 / 60Hz | ||||
| Power Factor Range | 0.8 leading ~ 0.8 lagging | ||||
| Max. Continuous Current Input / Output | 90.8 / 45.4A | 91.2 / 45.6A | 121.6 / 60.8A | 152 / 76A | 182.4 / 91.2A |
| Max. Output Overcurrent Protection | 68.1 / 64.7A | 68.4 / 65A | 91.2 / 86.6A | 114 / 108.3A | 136.7 / 129.9A |
| Battery | |||||
| Battery Type | Lithium / Lead-acid | ||||
| Battery Voltage Range | 135-850Vdc | ||||
| Rated Battery Voltage | 150Vdc | 150Vdc | 200Vdc | 250Vdc | 300Vdc |
| Max. Charge Current | 2 × 100A | ||||
| Max. Discharge Current | 2 × 100A | ||||
| Reverse Connect Protection | Yes | ||||
| PV Input | |||||
| Number of MPPT Trackers / Strings | 4 / 2 + 2 + 2 + 2 | ||||
| Max. PV Input Power | 59.8kW | 60kW | 80kW | 100kW | 100kW |
| Max. DC Voltage | 1000Vdc | ||||
| MPPT Voltage Range | 150-850Vdc | ||||
| Start-up Voltage | 200Vdc | ||||
| Max. Input Current per String | 8 × 20A | ||||
| Isc PV Absolute Maximum per String | 8 × 30A | ||||
| AC Output EPS / Generator | |||||
| EPS Rated Output Voltage | 380 / 400Vac, 3W + N + PE | ||||
| EPS Rated Output Frequency | 50 / 60Hz | ||||
| EPS Rated Output Active Power | 29.9kW | 30kW | 40kW | 50kW | 60kW |
| EPS Rated Output Apparent Power | 29.9kVA | 30kVA | 40kVA | 50kVA | 60kVA |
| EPS Rated Output Current | 45.4 / 43.2A | 45.6 / 43.3A | 60.8 / 57.7A | 76 / 72.2A | 91.2 / 86.6A |
| Overload Capacity Off Grid | 110% 30s / 120% 10s / 150% 0.2s | ||||
| Efficiency | |||||
| MPPT Efficiency | 99.90% | ||||
| Euro Efficiency | 97.50% | ||||
| Max. Efficiency | 98.50% | ||||
| Protection & Feature | |||||
| Insulation Monitoring | Yes | ||||
| Residual Current Monitoring | Yes | ||||
| Parallel Function | Yes, up to 8 pcs | ||||
| Protection Degree | IP66 | ||||
| Certifications | IEC 62109-1/2, IEC 62477-1, IEC 61000-6-2, IEC 61000-6-4, EN 50549-1 & -10, NRS 097-2-1 | ||||
| Other Protection | Ground fault current monitoring, earth fault detection, residual current detection and other protection functions | ||||
| General Parameter | |||||
| Storage Temperature | -25°C ~ +60°C | ||||
| Operating Temperature | -25°C ~ +60°C, linearly derating to 60% when exceeding +45°C ~ +60°C | ||||
| Humidity | 0% - 100%, non-condensing | ||||
| Max. Operating Altitude | 4000m | ||||
| Noise | <65dB | ||||
| Machine Dimensions W × H × D | 544 × 880 × 278 mm | ||||
| Machine Weight / N.W. | 88 kg | ||||
| Display & Communication | |||||
| Display | App + LED / LCD -S version | ||||
| Interface | RS485 / Wi-Fi / CAN / DRM, optional Bluetooth / LAN / Meter | ||||